Please use this identifier to cite or link to this item: http://bura.brunel.ac.uk/handle/2438/24924
Full metadata record
DC FieldValueLanguage
dc.contributor.authorAboshady, F-
dc.contributor.authorThomas, D-
dc.contributor.authorSumner, M-
dc.date.accessioned2022-07-18T11:20:15Z-
dc.date.available2022-07-18T11:20:15Z-
dc.date.issued2020-04-07-
dc.identifier.citationAboshadym, F., Thomas, D. and Sumner, M. (2020) 'A Fault Location Scheme for Active Untransposed Distribution Systems Using a Limited Number of Synchronized Measurements', Electric Power Components and Systems, 48 (1-2), pp. 1 - 11. doi: 10.1080/15325008.2020.1731880.en_US
dc.identifier.issn1532-5008-
dc.identifier.urihttps://bura.brunel.ac.uk/handle/2438/24924-
dc.description.abstractThis paper presents a fault location scheme for unbalanced and untransposed distribution systems which contain different types of distributed generation (DG). A general formula has been derived for any fault type using a limited number of synchronized measurement points. To avoid having to synchronize all the measurement points, the voltage and current measured locally at the DGs are processed locally to calculate the equivalent impedance of the DG at the non-fundamental frequencies. This is then used in the fault location process. The IEEE 34-bus feeder is simulated using the distributed parameter model for the lines and is used to validate the proposed scheme. Uncertainties associated with fault type, fault location, fault resistance, inception angle, noise in measurements and load profile are considered in the evaluation. The simulation studies demonstrate that the scheme can have a high accuracy and is robust.en_US
dc.format.extent1 - 11-
dc.format.mediumPrint-Electronic-
dc.languageEnglish-
dc.language.isoen_USen_US
dc.publisherRoutledge (Taylor & Francis Group)en_US
dc.rightsCopyright © 2020. This is an Accepted Manuscript of an article published by Taylor & Francis in Electric Power Components and Systems on 07 Apr 2020, available online: https://www.tandfonline.com/doi/full/10.1080/15325008.2020.1731880.-
dc.rights.urihttps://creativecommons.org/licenses/by-nc/4.0/-
dc.subjectdistributed generationen_US
dc.subjectdistribution systemsen_US
dc.subjectfault locationen_US
dc.subjectfault transienten_US
dc.subjectimpedance baseden_US
dc.titleA Fault Location Scheme for Active Untransposed Distribution Systems Using a Limited Number of Synchronized Measurementsen_US
dc.typeArticleen_US
dc.identifier.doihttps://doi.org/10.1080/15325008.2020.1731880-
dc.relation.isPartOfElectric Power Components and Systems-
pubs.issue1-2-
pubs.publication-statusPublished-
pubs.volume48-
dc.identifier.eissn1532-5016-
dc.rights.holderInforma UK Limited, trading as Taylor & Francis Group-
Appears in Collections:Dept of Mechanical and Aerospace Engineering Research Papers

Files in This Item:
File Description SizeFormat 
FullText.pdfCopyright © 2020. This is an Accepted Manuscript of an article published by Taylor & Francis in Electric Power Components and Systems on 07 Apr 2020, available online: https://www.tandfonline.com/doi/full/10.1080/15325008.2020.1731880.375.88 kBAdobe PDFView/Open


This item is licensed under a Creative Commons License Creative Commons