Please use this identifier to cite or link to this item: http://bura.brunel.ac.uk/handle/2438/19447
Title: Optimal network reconfiguration in active distribution networks with soft open points and distributed generation
Authors: Diaaeldin, I
Aleem, SA
El-Rafei, A
Abdelaziz, A
Zobaa, AF
Keywords: distributed generation;load balancing;network reconfiguration;optimization;power;loss minimization;soft open points
Issue Date: 30-Sep-2019
Publisher: MDPI
Citation: Diaaeldin, I., Abdel Aleem, S., El-Rafei, A., Abdelaziz, A. and Zobaa, A.F. (2019) ‘Optimal Network Reconfiguration in Active Distribution Networks with Soft Open Points and Distributed Generation’, Energies, 12 (21), 4172, pp. 1-31. doi: 10.3390/en12214172.
Abstract: Copyright © 2019 by the authors. In this study, we allocated soft open points (SOPs) and distributed generation (DG) units simultaneously with and without network reconfiguration (NR), and investigate the contribution of SOP losses to the total active losses, as well as the effect of increasing the number of SOPs connected to distribution systems under different loading conditions. A recent meta-heuristic optimization algorithm called the discrete-continuous hyper-spherical search algorithm is used to solve the mixed-integer nonlinear problem of SOPs and DGs allocation, along with new NR methodology to obtain radial configurations in an efficient manner without the possibility of getting trapped in local minima. Further, multi-scenario studies are conducted on an IEEE 33-node balanced benchmark distribution system and an 83-node balanced distribution system from a power company in Taiwan. The contributions of SOP losses to the total active losses, as well as the effect of increasing the number of SOPs connected to the system, are investigated to determine the real benefits gained from their allocation. It was clear from the results obtained that simultaneous NR, SOP, and DG allocation into a distribution system creates a hybrid configuration that merges the benefits offered by radial distribution systems and mitigates drawbacks related to losses, power quality, and voltage violations, while offering a far more efficient and optimal network operation. Also, it was found that the contribution of the internal loss of SOPs to the total loss for different numbers of installed SOPs is not dependent on the number of SOPs and that loss minimization is not always guaranteed by installing more SOPs or DGs along with NR. One of the findings of the paper demonstrates that NR with optimizing tie-lines could reduce active losses considerably. The results obtained also validate, with proper justifications, that SOPs installed for the management of constraints in LV feeders could further reduce losses and efficiently address issues related to voltage violations and network losses.
URI: https://bura.brunel.ac.uk/handle/2438/19447
DOI: https://doi.org/10.20944/preprints201909.0339.v1
Other Identifiers: 4172
Appears in Collections:Dept of Electronic and Electrical Engineering Research Papers

Files in This Item:
File Description SizeFormat 
FullText.pdf1.81 MBAdobe PDFView/Open


This item is licensed under a Creative Commons License Creative Commons