Please use this identifier to cite or link to this item: http://bura.brunel.ac.uk/handle/2438/12378
Full metadata record
DC FieldValueLanguage
dc.contributor.authorAbdel Aleem, S-
dc.contributor.authorIbrahim, A-
dc.contributor.authorZobaa, A-
dc.date.accessioned2016-03-21T10:17:59Z-
dc.date.available2016-03-17-
dc.date.available2016-03-21T10:17:59Z-
dc.date.issued2016-
dc.identifier.citationThe Journal of Engineering, 1(1): pp. 1 - 25, (2016)en_US
dc.identifier.issn2051-3305-
dc.identifier.urihttp://digital-library.theiet.org/content/journals/10.1049/joe.2016.0002-
dc.identifier.urihttp://bura.brunel.ac.uk/handle/2438/12378-
dc.description.abstractPower systems suffer from harmonic distortion and extra ohmic losses associated with them. Moreover, all harmonic frequencies are mostly assumed to have the same effect on the system losses. However, the frequency-dependency of the resistances should be taken into account, so that the apparent power and the power factor have to considerably reflect power losses under nonsinusoidal conditions. In this paper, the difference between unweighted and weighted non-sinusoidal losses, is addressed. A new harmonic-adjusted total harmonic distortion definition is proposed for both voltage and current. Besides, a new formula that relates the proposed harmonic-adjusted total harmonic distortion and a generalised harmonic derating factor definition of the frequency dependent losses of the power transmission and distribution equipment, is derived. An optimal C-type passive filter design for harmonic mitigation and power factor correction based on the minimisation of the proposed harmonic-adjusted total harmonic distortion for a balanced nonsinusoidal system is introduced. A comparative study of the proposed filter design based on the new harmonic-adjusted definition, and a conventional filter design based on standard total harmonic distortion definition, is presented.en_US
dc.format.extent1 - 25-
dc.language.isoenen_US
dc.publisherInstitution of Engineering and Technologyen_US
dc.subjectCable deratingen_US
dc.subjectHarmonic distortionen_US
dc.subjectNon-sinusoidal conditionsen_US
dc.subjectPower qualityen_US
dc.subjectResonanceen_US
dc.subjectTransformer deratingen_US
dc.titleHarmonic assessment based adjusted current total harmonic distortionen_US
dc.typeArticleen_US
dc.identifier.doihttp://dx.doi.org/10.1049/joe.2016.0002-
dc.relation.isPartOfThe Journal of Engineering-
pubs.publication-statusPublished-
Appears in Collections:Dept of Electronic and Electrical Engineering Research Papers

Files in This Item:
File Description SizeFormat 
Fulltext.pdf431.86 kBAdobe PDFView/Open


Items in BURA are protected by copyright, with all rights reserved, unless otherwise indicated.